Main data
| Nominal load voltage | 240 V AC |
| Nominal input voltage | 5 V DC |
| Rated load current | 2,5 A |
| MTTF (MIL-HDBK-217F) | 365,3 years |
Control circuit
| Input voltage max. | 7 V DC |
| Switch-on voltage | 2,7 V DC |
| Switch-off voltage | 2,5 V DC |
| Power consumption | 65 mW |
| Input impedance | 0,3 kO |
Load circuit
| Load current range | 0 - 2,5 A, no minimum load required |
| Load voltage range | 0 - 265 V AC, no minimum load required |
| Inrush current | 90 A, 20 ms |
| Voltage drop | 1 V |
| Switch-on time | 1 ms |
| Switch-off time | 11 ms |
Isolation
| isolation method | Pulse transformer (an unique feature for Delcon relay compared to opto) |
| Test voltage input/output | 4600 V ACrms / 1 s |
| Overvoltage category | III |
| Pollution degree | 2 |
| Air/creepage distance I/O | 8 mm |
General data
| Operating temperature | -25 °C to +70 °C |
| Weight | 30 g |
| Housing material flammability | UL 94 V-0 |
| Package size | 100 |