Main data
| Nominal load voltage | 300 V DC |
| Nominal input voltage | 24 V DC |
| Rated load current | 5 A |
| MTTF (MIL-HDBK-217F) | 137 years |
Control circuit
| Input voltage max. | 32 V DC |
| Switch-on voltage | 16 V DC |
| Switch-off voltage | 14 V DC |
| Power consumption | 288 mW |
| Input impedance | 2 kO |
Load circuit
| Load current range | 0 - 5 A DC, no minimum load required |
| Load voltage range | 0 - 380 V DC, no minimum load required |
| Inrush current | 20 A, 10 ms |
| Max. Inductive load, L/R | 5 ms (380 V, 5 A) |
| Max. Inductive load, L/R | 50 ms (24 V, 5 A) |
| Leakage current | 1 mA |
| Voltage drop | 0,6 V |
| Switch-on time | 0,3 ms |
| Switch-off time | 0,3 ms |
Isolation
| isolation method | Pulse transformer (an unique feature for Delcon relay compared to opto) |
| Test voltage input/output | 4600 V ACrms / 1 s |
| Overvoltage category | III |
| Pollution degree | 2 |
| Air/creepage distance I/O | 8 mm |
General data
| Conductor size, screw terminal | 2,5 mm2 |
| Conductor size, spring terminal | 0,75 - 2,5 mm2 |
| Operating temperature | -40 °C to +70 °C |
| Weight | 40 g |
| Housing material flammability | UL 94 V-0 |
| Package size | 10, 50 and 100 |